0422 Commissioning ZX5 Software 2018
Auteur Gareth Green | Dernière modification 9/10/2020 par Gareth Green en cours de rédaction ⧼frevu-button-review-label⧽
Pas encore d'image
0422 Commissioning ZX5 Software 2018
comissioning, ZX5, Software
Follow technical bulletin 409 to setup PC with correct naming conventions and TeamViewer.
Install TwinCAT 3.16 from the mainserver (G:\Design\TwinCAT3\TC31-Full-Setup.3.1.4022.16). Go through the wizard and when prompted restart the PC. (2019 PCs will have this)
Once restarted the TwinCAT icon will appear in the bottom right toolbar. We can now set up a route. Left click the TwinCAT icon once. There will be a menu, go to "Route" then "Add Route...". This is where the machine and the program can be linked. Making sure the machine infeed is on and connected to the local network,
There are two ways to approach this
Select Auto-start boot project. This can be found under PLC > PLC_Reset_1_1 and PLC > tc3Multi_6_24
Make sure to log onto the machine in tc3Multi AND PLCreset
Select from the dropdown box at the top (1) and click the green Download icon (2)
Note - this needs to be done for both PLCReset and tc3Multi.
If this is the first time, you will be asked to create the port, click OK
Please see TB0371 for all parameters than need change.