AMI TwinSAFE Workaround - Safety Project Creation

Auteur avatarGareth Green | Dernière modification 18/03/2025 par Gareth Green en cours de rédaction

How to create an AMI safety project to make a TwinSAFE AMI drive / motor compatible with a non-twinSAFE environment

Create the Safety Project

  • Add new Safety Project with preconfigured Input
  • Target System - Link to safety PLC on correct axis
  • Alias Devices->Add AM891x
  • Create the safeOr in TwinSafeGroup
  • Connect back on itself as per diagram
Preparing a C0001401B for TwinSAFE Project OrOut.png
  • OrIn1 is a break contact
  • Assign the variable name AlwaysTrue to orOut
  • Change the linking mode of the AMI to "Local"

Variable Mapping

Preparing a C0001401B for TwinSAFE Project Image Variable Mapping.png


  • AlwaysTrue to AMI891x as diagram
  • PLC Outputs
    • bErrAck -> ErrorAcknowledgement.sds
    • bSafetyRun->Run.sds
Preparing a C0001401B for TwinSAFE Project Image Link to PLC.png


See Also

Adding TwinSAFE projects to AMI Motors

Downloading AMI Motor Safety Project

Preparing a C0001401B for TwinSAFE Project