|Step_Title=<translate>Check the Labelling is correct</translate>
 +
|Step_Content=<translate>The turrets should be labelled 1-6 with pneumatic pipe markers
 +
 +
The turret position should be written on the top of each turret in permanent marker
 +
 +
{{Warning|...Take care to ensure the number match to the actual positions fed back from the binary inputs}}<br /></translate>
 
}}
 
}}
 
{{Tuto Step
 
{{Tuto Step

Version actuelle datée du 29 mars 2022 à 08:09

Auteur avatarAnonymous | Dernière modification 29/03/2022 par Gareth Green en cours de rédaction

Pas encore d'image

Commonly used during sawing on Z transoms, the Z block operation is used to fasten the profile, making sure it does not move during sawing.

Introduction

Commonly used during sawing on Z transoms, the Z block operation is used to fasten the profile, making sure it does not move during sawing. There are 6 possible states the z block can be in. Each of these can have a different length of protrusion for different profiles.


12 x M8 Screws

12 x M8 Nuts

12 x wire numbers 1 - 6

Étape 1 - Turret A - Find Position 1 on the Turret

On the Service > IO tab use output Y214 to turn the infeed turret.



Étape 2 - Check the Binary Count of the Turret

Each turn of the turrets will change the binary state of the inputs X210, X220 and X212.

Use the table in the picture to ensure the count goes 1-2-3-4-5-6 and back to 1



Étape 3 - Repeat for the outfeed turret

Use Y215 to pulse the outfeed turret

Each turn of the turrets will change the binary state of the inputs X211, X221 and X213

Use the table in the picture to ensure the count goes 1-2-3-4-5-6 and back to 1



Étape 4 - Check the Labelling is correct

The turrets should be labelled 1-6 with pneumatic pipe markers

The turret position should be written on the top of each turret in permanent marker

...Take care to ensure the number match to the actual positions fed back from the binary inputs

Étape 5 - Check Turret Home for Infeed and Outfeed turret

X214 InF_ZIHome should signal high (red) when the infeed turret is home

X215 InF_ZOHome should signal high (red) when the outfeed turret is home