[version en cours de rédaction] | [version en cours de rédaction] |
(Une révision intermédiaire par le même utilisateur non affichée) | |||
Ligne 23 : | Ligne 23 : | ||
=Easy Start Guide= | =Easy Start Guide= | ||
− | {{#annotatedImageLight:Fichier:WEG Inverter Setup WEG.JPG|0=603px|hash=|jsondata=|mediaClass=Image|type=frameless|align=center|src=https://stuga.dokit.app/images/6/63/WEG_Inverter_Setup_WEG.JPG|href=./Fichier:WEG Inverter Setup WEG.JPG|resource=./Fichier:WEG Inverter Setup WEG.JPG|caption=|size=603px}} | + | {{#annotatedImageLight:Fichier:WEG Inverter Setup WEG.JPG|0=603px|hash=|jsondata=|mediaClass=Image|type=frameless|align=center|src=https://stuga.dokit.app/images/6/63/WEG_Inverter_Setup_WEG.JPG|href=./Fichier:WEG Inverter Setup WEG.JPG|resource=./Fichier:WEG Inverter Setup WEG.JPG|caption=|size=603px}} |
+ | |||
+ | = Parameters = | ||
{| class="wikitable" | {| class="wikitable" | ||
|+Parameter Settings | |+Parameter Settings | ||
Ligne 145 : | Ligne 147 : | ||
|} | |} | ||
− | + | =Further Information= | |
− | + | [https://static.weg.net/medias/downloadcenter/hf5/h40/WEG-cfw100-programming-manual-10002853582-2.3x-manual-english.pdf Programming Manual] | |
<br /></translate> | <br /></translate> |
How to set up the WEG inverters. used on the Transfer crank and Infeed modules.
Auteur Stuga Engineer | Dernière modification 28/10/2024 par Gareth Green en cours de rédaction ⧼frevu-button-review-label⧽
How to set up the WEG inverters. used on the Transfer crank and Infeed modules.
WEG_Inverter_Setup_WEG_INV.jpg
Date | Photo | |
---|---|---|
2021 | Original Unit fitted due to supply chain issues with Eaton Motor Starters | |
2024 | IO Module added to allow a fault signal to be fed back to control system
see ECN004 WEG Inverter Update - Fault Output ...Additional parameters needed when using IO block
|
Number | Setting | Function | Notes |
---|---|---|---|
P100 | Accel Time | See Below | |
P101 | Decel Time | See Below | |
P133 | 50 | Min Frequency Ref | |
P134 | 50 | Max Frequency Ref | |
P271 | 1 | Set DIx to 24v DC | |
P220 | 1 | Remote Selection | |
P226 | 4 | Remote Rotate Selection | |
P227 | 1 | Remote Run Selection | |
P263 | 4 | DI1 Function (FWD) | |
P264 | 5 | DI2 Function (REV) | |
P265 | 20 | DI3 Function (RESET) | Only Used when IO Module is fitted to front of unit |
P266 | 40 | DI4 Function (ESTOP) | |
P275 | 13 | DO1 Function (FAULT) |
Machine Type | Inverter Location
(Module Panel) |
Motor Location
(Module) |
Motor | P100 | P101 |
---|---|---|---|---|---|
ZX5 | A | A | Infeed Conveyor | 0.1 | 0.1 |
A | A | Infeed Wheel | 0.1 | 0.1 | |
B | C | Crank | 0.5 | 0.1 | |
B | D | Crank | 1.0 | 0.2 | |
B | E | Crank | 0.5 | 0.1 | |
Autoflow Mk4 | B | A | Infeed conveyor | 0.5 | 0.5 |
en
none
0
Published
Vous avez entré un nom de page invalide, avec un ou plusieurs caractères suivants :
< > @ ~ : * € £ ` + = / \ | [ ] { } ; ? #