Étape 1 - Plug programming lead and run DrivesConnect Software

Programming lead is kept at Stuga

Software can be downloaded at

http://www.drive-support-studio.com/OTS/Eaton/downloads/deploy/drivesConnect.htm

Étape 2 - Scan Network for Drive

Click on Scan Drive Network to find the drive you are plugged in to

Étape 3 - Set Parameters

  1. Set Accel to 0.1s
  2. Set Decel to 0.1s
  3. Unlock Extended Parameters - Set P14 to 101. This creates the "Extended" tab on the top



Étape 4 - Set Config Mode

Click on the Extended tab

Set the P15 Config Mode to 2, which means [Fwd][Rev][Freqbit1][FreqBit2]



Étape 5 - Set Frequency References

Set these references P-20 to P-23 to 50Hz so it will not matter what input 3 or 4 is set to - it will always be 50Hz



Étape 6 - Transfer Current Data Set to Drive

Press the button in the top toolbar with a picture of the drive and a red arrow