Étape 1 - Plug programming lead

Étape 2 - Scan Network for Drive

Click on Scan Drive Network to find the drive you are plugged in to

Étape 3 - Unlock Extended Parameters

Set P14 to 101. This creates the "Extended" tab on the top



Étape 4 - Set Config Mode

Set the P15 Config Mode to 2, which means [Fwd][Rev][Freqbit1][FreqBit2]



Étape 5 - Set Frequency References

Set these references P-20 to P-23 to 50Hz so it will not matter what input 3 or 4 is set to - it will always be 50Hz