TB0287 Importance of Outfeed Clear Sensor

Auteur avatarGareth Green | Dernière modification 26/09/2019 par Gareth Green en cours de rédaction

Pas encore d'image

Following an H&S Incident (0005 – Nova Profile Ejecting), all flowlines and ZXs need to be checked to ensure the “Outfeed Clear” sensor is working. The incident proved that if the sensor fails, the outfeed may not be clear and hence the profile can be pushed back through the machine.

Technical Bulletin

TB Number: 287
Originator: Gareth Green
Machine: Flowlines, ZX
Date: 18/08/2015
Circulate to: Service
Title: Importance of Outfeed Clear Sensor

Problem

Following an H&S Incident (0005 – Nova Profile Ejecting), all flowlines and ZXs need to be checked to ensure the “Outfeed Clear” sensor is working. The incident proved that if the sensor fails, the outfeed may not be clear and hence the profile can be pushed back through the machine.

Resolution

A software update should be installed (contact GG) and the sensor tested for correct function.

The “useOutfeedClear” parameter should be switched on. This software update checks the sensor for the on state before ejecting, and then the off state after ejecting to check that the sensor is functional and not “always off”.

** REMEMBER TO CHECK ON DARK PROFILE if using an opto sensor**

It is possible to upgrade to using an ultrasonic sensor - see https://stuga.dokit.app/wiki/TB0394_Fitting_Ultrasonic_Sensor_to_Flowline_OCLEAR


If the part is faulty, it needs to be replaced with:

1 off E0000231 sensor

1 off E0000375 cable


A ZX3 / 4 machine may not have this part fitted and would need the following kit (see TB0161 for fitting, but ignore software part as this is for Neuron machines).


Photos
ZX3/4 Mounting Flowline Mounting
TB0287 Importance of Outfeed Clear Sensor 287-1.jpg
TB0287 Importance of Outfeed Clear Sensor 287-2.jpg


                             

          