Upgrade Flowline Opto Sensors to Ultrasonic : Différence entre versions

[version en cours de rédaction][version en cours de rédaction]
 
Ligne 8 : Ligne 8 :
 
}}
 
}}
 
{{Introduction
 
{{Introduction
|Introduction=<translate>With the development of full colour ranges for profiles, the older flowline opto sensors often have trouble "seeing" the darker profiles. An upgrade kit is available (R0019014) to replace the optical sensors with an ultrasonic version</translate>
+
|Introduction=<translate>With the development of full colour ranges for profiles, the older flowline opto sensors often have trouble "seeing" the darker profiles. An upgrade kit is available (R0019014) to replace the optical sensors with an ultrasonic version
 +
 
 +
<br /></translate>
 
}}
 
}}
 
{{Materials
 
{{Materials
Ligne 15 : Ligne 17 :
 
}}
 
}}
 
}}
 
}}
 +
{{EPI}}
 
{{Tuto Step
 
{{Tuto Step
 
|Step_Title=<translate>Kit of Parts</translate>
 
|Step_Title=<translate>Kit of Parts</translate>

Version actuelle datée du 31 mars 2020 à 15:02

Auteur avatarGareth Green | Dernière modification 31/03/2020 par Stuga Engineer en cours de rédaction

Upgrade Flowline Opto Sensors to Ultrasonic IMG 0130 - Copy.jpg

Upgrading the 3 off opto sensors on a flowline Mk3 infeed table to ultrasonic version

Introduction

With the development of full colour ranges for profiles, the older flowline opto sensors often have trouble "seeing" the darker profiles. An upgrade kit is available (R0019014) to replace the optical sensors with an ultrasonic version


Étape 1 - Kit of Parts



Étape 2 - Mechanical Fitting


Étape 3 - Wiring

The sensor wiring directly replaces the 3 other sensors


Étape 4 - Blower

The blower should Tee in to the blower already there for the other offcut measurement sensors