Instructions for performing pneumatic test on completed module
Auteur Gareth Green | Dernière modification 11/12/2023 par Gareth Green en cours de rédaction ⧼frevu-button-review-label⧽
Instructions for performing pneumatic test on completed module
R0015268_Pneumatic_module_Test_Screenshot_2023-07-05_113657.png
Tools Required
Ensure area is clear and free from personnel
Connect mains air supply and check for any leaks present is components natural state
Check home positions are correct in natural state
Loader wheel Y154 should be up away from roller beds in home position
Roller beds Y157 should be in the up position in home position
Blowers Y375 should be switched off in the home position
On valve bank, manually fire Y154 output.
Check for air leaks when output is fired
Check regulator shows pressure when fired by increasing pressure with adjusted .Once confirmed correct operation, a djust regulator to 1 bar or 0.1 mpa
On valve bank, manually fire valve Y157 roller lift output
All rollers should drop down into position. When fired, check there are no air leaks present in the active position
Manually fire Y357 output Check each blowers flow regulator can adjust flow rate when turned . Once confirmed , fully close flow regulator and wind out 2 turns