JetMove Error Messages

Auteur avatarGareth Green | Dernière modification 24/01/2023 par Gareth Green en cours de rédaction

Pas encore d'image

Jetta Jetmove Motor Fault table

JetMove 215B-480 - Table of Motor Faults

JetMove 215B-480 - Table of Motor Faults

Fault Number Type of Fault Description Error Response Rectification
Fault Number Type of Fault Description Rectification
F 00 Hardware error Internal hardware defect Immediate controller disable –   Separate the drive controller from the power lines

–   Return the amplifier for repair

F 01 Internal power supply error One or more power supply voltages are beyond their limits. Immediate controller disable –   Separate the drive controller from the power lines

–   Return the amplifier for repair

F 02 Mains phase error The motion system has detected failure of one of the mains phases. Immediate controller disable Check fuses and wiring Acknowledge failure
F 03 Motor cable breakage The motor cable is broken.

Please note: The motor cable is tested at enabling the controller for the first time.

Immediate controller disable Check the motor cable connections Acknowledge failure
F 04 Overvoltage in the DC link A DC link voltage > 850 V has been detected. Immediate controller disable Check input power supply

If the motor is used as a generator, reduce the regenerating power Acknowledge failure

F 05 Current overload Output current was greater than 2.5 x rated current Immediate controller disable Check motor cable for short circuit between lines or lines to earth

–   Check the current controller parameters. If necessary, correct the parameters –   Acknowledge failure

F 06 Ballast resistor overload The ballast resistor has been overloaded Immediate controller disable Let the amplifier cool down

When the motor has cooled down, acknowledge failure Reduce regeneration power

F 07 Amplifier overtemperature The amplifier has reached the maximum temperature Immediate controller disable Let the amplifier cool down

When the motor has cooled down, acknowledge failure Reduce power of the motion system

F 08 Motor overtemperature The motor has reached the maximum temperature

Also refer to “Built-in thermal sensor", page 39

Immediate controller disable Let the motor cool down

When the motor has cooled down, acknowledge failure Reduce the average load of the motor

F 09 Encoder failure Encoder breakage or initialization error Immediate controller disable For extended diagnostics purposes use Motion Setup Check the encoder line and all plug-in connections Acknowledge failure
F 10 Overspeed The actual shaft speed has exceeded a value of

1.25 x maximum speed

Immediate controller disable Check motor and encoder connections Control the speed parameters. Change parameters if necessary Acknowledge failure
F 11 Current overrange A current temporarily too high has been detected Immediate controller disable
F 14

(combined with F 00)

Internal communication error An internal communication error has occurred Immediate controller disable Switch the 24 V supply off and on again

If the error occurs repeatedly, return the amplifier for repair

F 15 The hardware enable is missing. The software enable is given without a hardware enable Immediate controller disable Disable the drive by means of the software Acknowledge failure
F 16 Power input overcurrent The current at the power input is too high Immediate controller disable Check input voltage Reduce mechanical power of the motor Acknowledge failure
F 17 Trip of software limit switch Actual position is outside the range of software limits; software limit switches are active Stop at max. current (max. torque)
F 18 Trip of hardware limit switch One hardware limit switch is active Stop at max. current (max. torque) Check target position Check reference position Acknowledge failure Return the axis within the hardware limits (the software limit

switches are activated automatically at entering this range)

F 20 Undervoltage in the DC link The DC link voltage is less than the set minimum value Stop with emergency deceleration ramp Check the supply voltage

Check parameter "Undervoltage DC link min. trip" Acknowledge failure

F 21 Overvoltage DC link voltage The DC link voltage has exceeded the set maximum value Stop with emergency deceleration ramp Check the supply voltage

In generator operation reduce braking power Acknowledge failure

F 22 The drive has stalled The drive was not able to exceed the n=0 threshold within the time limit specified by the parameter

"blocking-tripping time"

Immediate controller disable Eliminate the cause of stalling

Acknowledge failure

F 23 Tracking error The tracking error has exceeded the limit defined in the parameter "tracking error limit" for the time specified in "tracking error window time" Stop with emergency deceleration ramp Check the drive mechanism

Check steepness of acceleration/ deceleration ramps and amplifier parameters in relation to the parameters "tracking error limit" and "tracking error window time" Acknowledge failure

F 24

(combined with F 01)

Error in 24 V supply voltage The external 24 V supply has actually been lower than 18 V Immediate controller disable Check external power supply

Acknowledge failure

F 25 - F 27

(combined with F 01)

Internal power supply error One or more internal supply voltages have fallen below their limits Immediate controller disable
F 28 Error in power charging circuit The input current limitation circuit is defective Immediate controller disable
F 29 Mains power too high The average mains power of the 400/ 480 V supply has been too high Immediate controller disable Acknowledge failure Reduce the average load of the motor
F 30 I²t error The average power loss of the motor has been greater than the max. value configured by nominal motor current, overload factor and motor time constant.

Refer to “I²t calculation", page 39

Immediate controller disable Let the motor cool down

When the motor has cooled down, acknowledge failure Check the configuration of nominal motor current, overload factor and motor time constant Reduce the average load of the motor

F 31 Motor overload protection to UL Average motor power dissipation has been higher than defined according to UL. See chapter 5.2.3 "Motor overload protection according to UL", page 41 Immediate controller disable Let the motor cool down

Acknowledge failure Reduce the average load of the motor

F 38 Asymmetric encoder signal The amplitudes of the analog sine- cosine signals are not identical Immediate controller disable Check wiring or encoder signals Acknowledge failure
F 39 Error at commutation finding Measuring the commutation offset could not be completed with results being guaranteed Immediate controller disable Check parametering Check wiring or encoder signal Acknowledge failure
F 42 Malfunctioning of encoder 2 (only for the option CNT) Encoder breakage or initialization error Immediate controller disable Check the encoder line and all plug-in connections Acknowledge failure
...Alarms If the dot in the display is flashing, one or several alarms have been recognized. Please check either in the Motion Setup, or by issuing the motion instructions in the controller program, which alarm is active.