Preparing a C0001401B for TwinSAFE Project

Auteur avatarGareth Green | Dernière modification 18/03/2025 par Gareth Green en cours de rédaction

Pas encore d'image

Overcoming an issue with the DS402 protocol on the AMI8121-3100-0F21 motor

Problem

The specification of the GY and GZ motors on A2032 and A2033 included a TwinSAFE system, which makes it difficult to operate within a non-TwinSAFE environment.

Beckhoff have a solution to this, which is to use the TwinSAFE logic controller contained inside the AMI motor / drive to control its own STO "always on"


However

There is a problem with the particular spec of the AMI8121-3100-0F21 - the 2 denotes a DS402 communication interface profile. This profile needs a firmware update to enable the TwinSAFE communication.

Solution

The solution takes the following steps:

  • Ensure the TwinCAT environment is up to date
  • Ensure the latest ESI (device description tables) are downloaded
  • Ensure the latest